五月天手机无码av_色色图片区_97人人人人人人了_玖玖无码,免费无码片岛国在线看,A级毛片成年毛片20以上无码毛片,欧美成手机版在线视频,欧美一区高清,爱爱精品,成年轻人电影无码,h视频在线免费看

川消_萃聯(lián)
氣體滅火系統(tǒng)
自動噴水滅火系統(tǒng)

聯(lián)系我們

  • 萃聯(lián)(山東)消防設備有限責任公司
  • 電話:15508683119
  • 地址:山東省濟南市歷城區(qū)祝舜路44號
當前位置:首頁 > 新聞中心消防水泵的安裝應符合相關的規(guī)定要求

消防水泵的安裝應符合相關的規(guī)定要求

來源:http://www.n3462.cn/ 日期:2023-06-16

1,、消防水泵安裝前應校核產(chǎn)品合格證,以及其規(guī)格,、型號和性能與設計要求應一致,,并應根據(jù)安裝使用說明書安裝;
1. Before installing the fire water pump, the product certificate should be verified, and its specifications, models, and performance should be consistent with the design requirements. It should be installed according to the installation and operation manual;
2,、川消消防水泵安裝前應復核水泵基礎混凝土強度,、隔振裝置、坐標,、標高,、尺寸和螺栓孔位置;
2. Before installing the Sichuan Fire Water Pump, the foundation concrete strength, vibration isolation device, coordinates, elevation, size, and bolt hole position of the pump should be reviewed;
3,、消防水泵的安裝應符合現(xiàn)行標準《機械設備安裝工程施工及驗收通用規(guī)范》GB50231和《風機,、壓縮機、泵安裝工程施工及驗收規(guī)范》GB50275的有關規(guī)定,;
3. The installation of fire water pumps should comply with the relevant provisions of the current national standards "General Code for Construction and Acceptance of Mechanical Equipment Installation Engineering" GB50231 and "Code for Construction and Acceptance of Fan, Compressor, and Pump Installation Engineering" GB50275;
4,、消防水泵安裝前應復核消防水泵之間,以及消防水泵與墻或其他設備之間的間距,,并應滿足安裝,、運行和維護管理的要求;
4. Before installing the fire water pump, the spacing between the fire water pumps, as well as between the fire water pump and the wall or other equipment, should be reviewed and meet the requirements of installation, operation, and maintenance management;
川消
5,、消防水泵吸水管上的控制閥應在消防水泵固定于基礎上后再進行安裝,,其直徑不應小于消防水泵吸水口直徑,且不應采用沒有可靠鎖定裝置的控制閥,,控制閥應采用溝漕式或法蘭式閥門,;
5. The control valve on the suction pipe of the fire water pump should be installed after the fire water pump is fixed on the foundation. Its diameter should not be less than the diameter of the fire water pump suction port, and control valves without reliable locking devices should not be used. Control valves should be ditch or flange type valves;
6、當消防水泵和消防水池位于獨立的兩個基礎上且相互為剛性連接時,,吸水管上應加設柔性連接管,;
6. When the fire pump and fire pool are located on two independent foundations and are rigidly connected to each other, a flexible connecting pipe should be added to the suction pipe;
7、吸水管水平管段上不應有氣囊和漏氣現(xiàn)象,。變徑連接時,,應采用偏心異徑管件并應采用管頂平接,;
7. There should be no air pockets or leaks on the horizontal section of the suction pipe. When connecting with variable diameter, eccentric reducing pipe fittings should be used and the top of the pipe should be flat connected;
8、消防水泵出水管上應安裝消聲止回閥,、控制閥和壓力表,;系統(tǒng)的總出水管上還應安裝壓力表和壓力開關;安裝壓力表時應加設緩沖裝置,。壓力表和緩沖裝置之間應安裝旋塞;壓力表量程在沒有設計要求時,,應為系統(tǒng)工作壓力的2倍~2.5倍,;
8. Silencing check valves, control valves, and pressure gauges should be installed on the outlet pipe of the fire pump; A pressure gauge and pressure switch should also be installed on the main outlet pipe of the system; When installing a pressure gauge, a buffer device should be added. A cock should be installed between the pressure gauge and the buffer device; When there is no design requirement, the range of the pressure gauge should be 2 to 2.5 times the working pressure of the system;
9、消防水泵的隔振裝置,、進出水管柔性接頭的安裝應符合設計要求,,并應有產(chǎn)品說明和安裝使用說明。
9. The installation of the vibration isolation device and flexible joints of the inlet and outlet pipes of the fire water pump should meet the design requirements, and there should be product instructions and installation instructions.
消防水泵的安裝應符合相關的規(guī)定要求就講解到這里了,,希望能夠給您好的幫助,,更多事項就來我們網(wǎng)站http://www.n3462.cn咨詢!
The installation of fire water pumps should comply with relevant regulations and requirements. That's all. We hope to provide you with good help. For more information, please come to our website http://www.n3462.cn consulting service
上一篇:高壓細水霧滅火裝置還有哪些其它的選型,?
下一篇:圖像型火災探測器怎么布線效率高

相關產(chǎn)品 / Related products